WAGO-I/O-SYSTEM 750
Connect Devices
73
750-666/000-003 4FDI/2FDO 24V/10A PROFIsafe V2 iPar
Manual
Version 1.2.0, valid from HW/SW Version 01/01
Use the same value for the test pulse duration of output O1 and O2!
If the
Output Configuration
parameter is set to "H-Side/L-Side 1", the values of
the
Test pulse duration
for both outputs O1 and O2 must be set to the same
value. This is checked by the PROFIsafe I/O module during the parameterization
procedure and a suggested correction is indicated by the PROFIsafe I/O module in
the WAGO parameterization tool in case of deviation.
The value of the output tolerance time must not be less that the value of the
test pulse duration!
The value of the
Output tolerance time
parameter may not be less than the value
of the
Test pulse duration
parameter. This is checked by the PROFIsafe I/O
module during the parameterization procedure and a suggested correction is
indicated by the PROFIsafe I/O module in the WAGO parameterization tool in
case of deviation.