Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
649
7.6
GUI DISPLAY SETUP
Function Code:
G01
Version 1
Function Type:
Set Display Setup - System Status Configuration
Command Format:
Inquire:
Display:
<SOH>SG0100TTc
<SOH>IG0100TT
Computer:
<SOH>sG0100TTc
<SOH>iG0100TT
Notes:
1.
TT - Tab, 00=all Tabs
01=All Tanks Tab
02=All Sensors Tab
03=’User Defined 1’ Tab
04=’User Defined 2’ Tab
05=’User Defined 3’ Tab
2.
c - Configuration
0=Disabled
1=Enabled
Typical Response Message, Display Format:
<SOH>
IG010000
JAN 22, 1996 3:06 PM
Display Setup – System Status
Tab Name Configuration
All Tanks : Enabled
All Sensors : Disabled
‘Sump Devices’ Tab : Enabled
‘Prem Tank&Sens’ Tab : Disabled
‘User Defined 3’ Tab : Disabled
<ETX>
Typical Response Message, Computer Format:
<SOH>iG0100YYMMDDHHmmNNTTc...TTc&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
NN - Number of Fields To Follow
3.
TT - Tab
4.
c - Configuration
0=Disabled
1=Enabled
5.
&& - Data Termination Flag
6.
CCCC - Message Checksum