Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
457
Function Code:
7B4
Version 2
Function Type:
Set Individual Meter Offset
Command Format:
Inquire:
Display:
<SOH>S7B400 FF MM TT +0.00
<SOH>I7B400
Computer:
not supported
<SOH>i7B400
Notes:
1.
FF - Fueling Position (Decimal)
2.
MM - Meter Number (Decimal)
3.
TT - Tank Number (Decimal)
4.
o.oo - Meter Offset, percent (D/-9.99)
Typical Response Message, Display Format:
<SOH>
I7B400
JUN 1, 2013 8:10 AM
INDIVIDUAL METER OFFSET
FP METER TANK OFFSET
01 00 3 PREMIUM +0.00%
01 1 UNLEADED +0.00%
02 00 3 PREMIUM +0.00%
01 1 UNLEADED +0.00%
03 00 3 PREMIUM +0.00%
01 1 UNLEADED +0.00%
04 00 3 PREMIUM +0.00%
01 1 UNLEADED +0.00%
05 00 3 PREMIUM +0.00%
01 1 UNLEADED +0.00%
02 2 DIESEL +0.00%
06 00 3 PREMIUM +0.00%
01 1 UNLEADED +0.00%
02 2 DIESEL +0.00%
<ETX>
Typical Response Message, Computer Format:
<SOH>i7B400YYMMDDHHmmNNNNFFMMTToooooooo…
FFMMTToooooooo&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
NNNN - Number of entires to follow (ASCII Hex)
3.
FF - Fuel Position (Decimal)
4.
MM - Meter Position (Decimal)
5.
TT - Tank Number (Decimal)
00=Tank not mapped
6.
oooooooo - Meter Offset, Percent (Decimal, +/-9.99)
7.
&& - Data Termination Flag
8.