Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
388
Function Code:
P06
Version 1
Function Type:
Set Pump – Pump Sense Device
Command Format:
Inquire:
Display:
<SOH>SP06QQttff
<SOH>IP06QQ
Computer:
<SOH>sP06QQttff
<SOH>iP06QQ
Notes:
1.
Unassigned - To de-assign the Pump Sense Device the user must set both tt =
00 and ff = 00 for the operation to be valid.
2.
Pump Mode - Assignment of a Pump Sense Device is not allowed for a Pump
with a Pump Mode of “External Pump Control”.
Typical Response Message, Display Format:
<SOH>
IP06QQ
JAN 24, 1996 2:54 PM
PUMP SENSE DEVICES
PUMP DEVICE TYPE
DEVICE ID
Pm 1: EXTERNAL INPUT 1
<ETX>
Typical Response Message, Computer Format:
<SOH>iP06QQYYMMDDHHmmQQttff...
QQttff&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pump number (Decimal, 00=All)
3.
tt - Device Type (Decimal)
00 – NULL_DEV_TYPE
05 - External Input – (see 80F Input type - pump sense)
ff – Device ID (Decimal)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum