Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
444
Function Code:
79F
Version 2
Function Type:
Set BIR Temperature Compensation Flag
Command Format:
Inquire:
Display:
<SOH>S79F00f
<SOH>I79F00
Computer:
<SOH>s79F00f
<SOH>i79F00
Typical Response Message, Display Format:
<SOH>
I79F00
JAN 22, 2009 3:24 PM
TEMP COMPENSATION
STANDARD
<ETX>
Typical Response Message, Computer Format:
<SOH>i79F00YYMMDDHHmmf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
f - Status
0=Standard
1=TC Volume
3.
&& - Data Termination Flag
4.
CCCC - Message Checksum