Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
21
Function Code:
093
Version 1
Function Type:
Stop Pressure Line Leak Profile Line Test
Command Format:
Display:
<SOH>S093QQ149
Computer:
<SOH>s093QQ149
Notes:
1.
149 - This verification code must be sent to confirm the comand
Typical Response Message, Display Format:
<SOH>
S093QQ
NOV 14, 2001 10:15 PM
STOP PRESSURE LINE LEAK PROFILE LINE TEST
Q 1:UNLEADED REGULAR
STATUS: ABORTED
<ETX>
Typical Response Message, Computer Format:
<SOH>s093QQYYMMDDHHmmQQtt
QQtt&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
3.
tt - Test Status
00 = TEST COMPLETE (DONE: BULK MOD 10000)
01 = TURN PUMP ON (RUNNING PUMP)
02 = PUMP ON WAIT (RUNNING PUMP)
03 = PRESSURE 1 WAIT (PUMP OFF)
04 = PRESSURE 2 WAIT (MEASURING Pxx 19.123 PSI)
05 = CALC WAIT TIME (MEASURING Pxx 19.123 PSI)
06 = PRESSURE N WAIT (MEASURING Pxx 19.123 PSI)
07 = EVALUATE PERIOD (MEASURING Pxx 19.123 PSI)
08 = TEST ABORT (ABORTED)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum