Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
392
Function Code:
775
Version 1
Function Type:
Set Pressure Line Leak Profile Line Test Leak Rate
Command Format:
Inquire:
Display:
<SOH>S775QQrr.rr
<SOH>I775QQ
Computer:
<SOH>s775QQFFFFFFFF
<SOH>i775QQ
Notes:
1.
QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
2.
rr.rr - Profile Line Test Leak Rate, GPH (Decimal)
3.
FFFFFFFF - Profile Line Test Leak Rate, GPH (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I775QQ
JAN 14, 1995 10:15 PM
PRESSURE LINE LEAK PROFILE LINE TEST LEAK RATE
LINE TEST LEAK RATE
Q 1:UNLEADED REGULAR 3.00 GPH
<ETX>
Typical Response Message, Computer Format:
<SOH>s775QQYYMMDDHHmmQQFFFFFFFF
QQFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak Sensor Number (Decimal, 00 = all)
3.
FFFFFFFF - Profile Line Test Leak Rate, GPH (ASCII Hex IEEE float)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum