Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
280
Function Code:
60A
Version 1
Function Type:
Set Tank Linear Calculated Full Volume
Command Format:
Inquire:
Display:
<SOH>S60ATTGGGGGG
<SOH>I60ATT
Computer:
<SOH>s60ATTFFFFFFFF
<SOH>i60ATT
Notes:
1.
TT - Tank Number (Decimal, 00=all)
2.
GGGGGG - Full Height Volume, Gallons (Decimal)
3.
FFFFFFFF - Full Height Volume, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I60ATT
JAN 22, 1996 3:17 PM
TANK FULL VOLUME
TANK LABEL TANK PROFILE GALLONS
1 REGULAR UNLEADED 1 PT 10000
<ETX>
Typical Response Message, Computer Format:
<SOH>i60ATTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
FFFFFFFF - Full height volume (ASCII Hex IEEE float)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum