Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
555
Function Code:
A56
Version 1
Function Type:
CSLD Monthly Report
Command Format:
Display:
<SOH>IA56TTt
Computer:
<SOH>iA56TTt
NOTE:
The most current record from the previous month (if available) will be returned
if a record doesn’t exist for the current month.
Typical Response Message, Display Format:
<SOH>
IA56TT
OCT 25, 2000 10:00 AM
CSLD MONTHLY REPORT
CURRENT MONTH
0.2 GAL/HR TEST
T 1:UNLEADED GASOLINE
PROBE SERIAL NUM 627020
OCT 25, 2000 7:15 AM RESULT: No Results Available
OCT 24, 2000 3:22 PM RESULT: Pass
OCT 23, 2000 6:26 AM RESULT: Fail
OCT 20, 2000 12:44 PM RESULT: Increase
OCT 20, 2000 5:23 AM RESULT: Warning
OCT 19, 2000 8:23 AM RESULT: Invalid
OCT 18, 2000 9:53 PM STATUS: No Idle Data
OCT 16, 2000 6:14 AM STATUS: Active
<ETX>
Typical Response Message, Computer Format:
<SOH>iA56TTYYMMDDHHmmtTTNNYYMMDDHHmmrr...
TTNNYYMMDDHHmmrr&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
t - Report Type
0=Current Month
1=Previous Month
3.
TT - Tank Number (Decimal, 00=all)
4.
NN - Number of CSLD State Changes (12 char) to follow (Hex)
5.
YYMMDDHHmm - Date and Time of CSLD State Change
6.
rr - CSLD State Change:
01=RESULT: Pass
02=RESULT: Fail
03=RESULT: No Results Available
04=RESULT: Invalid
08=RESULT: Increase
09=RESULT: Warning
98=STATUS: No Idle Data
99=STATUS: Active
7.
&& - Data Termination Flag
8.
CCCC - Message Checksum