Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
479
Function Code:
807
Version 1
Function Type:
Set Relay Location Label
Command Format:
Inquire:
Display:
<SOH>S807RRaaaaaaaaaaaaaaaaaaaa
<SOH>I807RR
Computer:
<SOH>s807RRaaaaaaaaaaaaaaaaaaaa
<SOH>i807RR
Typical Response Message, Display Format:
<SOH>
I807RR
MAR 26, 1996 1:51 PM
RELAY LABEL
DEVICE LABEL
1 aaaaaaaaaaaaaaaaaaaa
<ETX>
Typical Response Message, Computer Format:
<SOH>i807RRYYMMDDHHmmRRaaaaaaaaaaaaaaaaaaaa...
RRaaaaaaaaaaaaaaaaaaaa&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
RR - Relay Number (Decimal, 00=all)
3.
a - Location Label (20 ASCII characters [20h-7Eh])
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum