Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
558
Function Code:
A58
Version 1
Function Type:
CSLD Diagnostics: Moving Average Table
Command Format:
Display:
<SOH>IA58TT
Computer:
<SOH>iA58TT
Typical Response Message, Display Format:
<SOH>
IA58TT
MAR 26, 1996 1:48 PM
CSLD DIAGNOSTICS: AGGREGATE ATG DATA QUEUE
T 1:REGULAR UNLEADED
SMPL AGGREG MOVING ERROR
DATE/TIME CNT TCVOL AVERAGE VARIANCE IDLE STATE FLAGS
------------ ---- -------- -------- -------- ---- ----------- -----
960326132554 31 3074.65 3074.65 45.86 NO NO TEST 0000
960326132624 30 3072.62 3072.62 45.86 NO PRE START 0000
960326132654 31 3072.46 3072.46 45.86 YES IN PROGRESS 0000
960326132724 30 3072.54 3072.54 45.86 YES COMPLETE 0000
960326132754 31 3073.13 3073.13 45.86 YES ABORT TEST 0000
960326132824 31 3072.97 3072.97 45.86 YES PRE DELAY 0000
960326132854 31 3072.97 3072.97 45.86 YES END DELAY 0000
<ETX>
Typical Response Message, Computer Format:
<SOH>iA5801YYMMDDHHmmTTNNssssssssnnccccccccmmmmmmmmvvvvvvvvISEEEE
ssssssssnnccccccccmmmmmmmmvvvvvvvvISEEEE
TTNNssssssssnnccccccccmmmmmmmmvvvvvvvvISEEEE&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=All Tanks)
3.
NN – Number of samples in queue (hex)
4.
ssssssss – time stamp in seconds since 1970 (ascii hex long)
5.
nn – number of probe readings (ascii hex)
6.
cccccccc – tc volume in gallons/liters (ascii hex float)
7.
mmmmmmmm – moving average in gallons/liters (ascii hex float)
8.
vvvvvvvv – variance (ascii hex float)
9.
I – 1=idle, 0=busy
10.
S - state
0=No test
1=Test pre-start
2=Test in-progress
3=Test complete
4=Abort test
5=Pre-delay
6=End delay
11.
EEEE – Error flags (ascii hex short)
12.
&& - Data Termination Flag
13.
CCCC - Message Checksum