Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
122
Function Code:
302
Version 1
Function Type:
Liquid Sensor Alarm History Report
Command Format:
Display:
<SOH>I302SS
Computer:
<SOH>i302SS
Typical Response Message, Display Format:
<SOH>
I302SS
JAN 28, 1995 10:10 AM
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
LIQUID ALARM HISTORY REPORT
SENSOR LOCATION
1 LIQUID # 1
JAN 6, 1995 8:02 AM FUEL ALARM
<ETX>
Typical Response Message, Computer Format:
<SOH>i302SSYYMMDDHHmmSSNNYYMMDDHHmmaaaa...
SSNNYYMMDDHHmmaaaa&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
SS - Sensor Number (Decimal, 00=all)
3.
NN - Number of Alarm Incidents to follow
4.
YYMMDDHHmm - Date and Time of Alarm
5.
aaaa - Alarm type number:
0001=Sensor Setup Data Warning
0002=Sensor Fuel Alarm
0003=Sensor Out Alarm
0004=Sensor Short Alarm
0005=Sensor Water Alarm
0006=Sensor Water Out Alarm
0007=Sensor High Liquid Alarm
0008=Sensor Low Liquid Alarm
0009=Sensor Liquid Warning
6.
&& - Data Termination Flag
7.