Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
360
7.3.7 SENSOR SETUP
Function Code:
701
Version 1
Function Type:
Set Liquid Sensor Configuration
Command Format:
Inquire:
Display:
<SOH>S701SSf
<SOH>I701SS
Computer:
<SOH>s701SSf
<SOH>i701SS
Typical Response Message, Display Format:
<SOH>
I701SS
JAN 28, 1995 10:39 AM
LIQUID CONFIGURATION
DEVICE LABEL CONFIGURED
1 LIQUID SENSOR #1 ON
<ETX>
Typical Response Message, Computer Format:
<SOH>i701SSYYMMDDHHmmSSf...
SSf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
SS - Liquid Sensor Number (Decimal, 00=all)
3.
f - Configuration Flag
0=Off
1=On
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum