Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
412
Function Code:
78C
Version 1
Function Type:
Set Pressure Line Leak 0.20 GPH Test Schedule
Command Format:
Inquire:
Display:
<SOH>S78CQQf
<SOH>I78CQQ
Computer:
<SOH>s78CQQf
<SOH>i78CQQ
Typical Response Message, Display Format:
<SOH>
I78CQQ
JAN 24, 1996 2:54 PM
PRESSURE LINE LEAK 0.20 TEST SCHEDULE
LINE 0.20 GPH TEST
Q 1:REGULAR UNLEADED MONTHLY
<ETX>
Typical Response Message, Computer Format:
<SOH>i78CQQYYMMDDHHmmQQf...
QQf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
f - 0.20 GPH Test Schedule
0=Disabled
1=Repetitive
2=Monthly
3=Manual
4.
&& - Data Termination Flag
5.