Function Code:
B46
Version 1
Function Type:
Type B Sensor (3 Wire CL) Diagnostic Report
Command Format:
Display:
<SOH>IB46SS
Computer:
<SOH>iB46SS
Typical Response Message, Display Format:
<SOH>
IB46SS
JAN 28, 1995 10:16 AM
SENSOR DIAGNOSTIC – 3-WIRE CL SENSOR INFORMATION REPORT
SINGLE SENSOR
SAMPLE
SENSOR CATEGORY COUNTER VALUE 1 VALUE 2 STATUS
1 PAN/SUMP:STANDARD 5 5200 100000 Normal
<ETX>
Typical Response Message, Computer Format:
<SOH>iB46SSYYMMDDHHmmSSNNFFFFFFFF...
SSNNFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
SS - Sensor Number (Decimal, 00=all)
3.
NN - Number of eight character Data Fields to follow (Hex)
4.
FFFFFFFF - ASCII Hex IEEE floats:
1. Sample Counter Value
2. High Reference Value 1
3. Low Reference Value 1
4. Last Reading 1
5. Current Average Value 1
6. High Reference Value 2
7. Low Reference Value 2
8. Last Reading 2
9. Current Average Value 2
5.
&& - Data Termination Flag
6.
CCCC - Message Checksum