Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
150
Function Code 385:
(Continued)
Typical Response Message, Computer Format:
<SOH>i385QQYYMMDDHHmmQQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt...
nnYYMMDDHHmmRRtt...
QQyymmddhhmmrrTTPPPPMMMMNNYYMMDDHHmmRRtt...
nnYYMMDDHHmmRRtt&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
yymmddhhmm - Last 3.00 gal/hr test time
4.
rr - 3.00 gal/hr test result (Hex)
5.
TT - 3.00 gal/hr test type (unused, always 00)
6.
PPPP - Number of 3.00 gal/hr tests passed in previous 24 hours (Hex)
7.
MMMM - Number of 3.00 gal/hr tests passed since midnight (Hex)
8.
NN - Number of 0.20 gal/hr test results (14 character groups) to
follow (Hex)
9.
YYMMDDHHmm - Date and time of 0.20 gal/hr test
10.
RR - Test result
01=PASS
02=FAIL
11.
tt - 0.20 gal/hr test type (unused, always 00)
12.
nn - Number of 0.10 gal/hr test results (14 character groups) to
follow (Hex)
13.
YYMMDDHHmm - Date and time of 0.10 gal/hr test
14.
RR - Test result
01=PASS
02=FAIL
15.
tt - 0.10 gal/hr test type (unused, always 00)
16.
&& - Data Termination Flag
17.
CCCC - Message Checksum