Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
406
Function Code:
782
Version 1
Function Type:
Set Pressure Line Leak Label
Command Format:
Inquire:
Display:
<SOH>S782QQaaaaaaaaaaaaaaaaaaaa
<SOH>I782QQ
Computer:
<SOH>s782QQaaaaaaaaaaaaaaaaaaaa
<SOH>i782QQ
Typical Response Message, Display Format:
<SOH>
I782QQ
JAN 24, 1996 2:54 PM
PRESSURE LLD LABEL
DEVICE LABEL
1 REGULAR UNLEADED
<ETX>
Typical Response Message, Computer Format:
<SOH>i782QQYYMMDDHHmmQQaaaaaaaaaaaaaaaaaaaa...
QQaaaaaaaaaaaaaaaaaaaa&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
a - Indicates any printable ASCII character
4.
&& - Data Termination Flag
5.