Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
539
Function Code:
A0X
Version 1
Function Type:
Probe Diagnostics - General
Command Format:
Display:
<SOH>IA0XPP
Computer:
<SOH>iA0XPP
Typical Response Message, Display Format:
<SOH>
IA0XTT
JAN 22, 2007 3:25 PM
PROBE 1:
- TANK
1
Serial Date
Type Code Length No Yr/Wk Rev Gradient
MAG3 C000 96.00 107611 x2/07 1 178.1400
MAG3 C000 96.00 107611 x2/07 1 178.1400
MAG3 C000 96.00 107611 x2/07 1 178.1400
<ETX>
Typical Response Message, Computer Format:
<SOH>iA0XTTYYMMDDHHmmPPTTrrCCCCyymmllllllllggggggggssssssssnn....
PPTTrrCCCCyymmllllllllggggggggssssssssnn....&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2. PP – Probe Number (Deciamal – 00=all)
3.
TT - Tank Number
4. rr -Revision (hex)
5.
CCCC - Probe Code (hex)
6.
YYMM - Year and Month Built (decimal)
7.
llllllll - Probe Length (ASCII Hex IEEE float)
8.
gggggggg - Gradient (ASCII Hex IEEE float)
9.
ssssssss - Serial Number (ASCII Hex IEEE long)
10.
&& - Data Termination Flag
11.
CCCC - Message Checksum