Function Code:
11C
Version 1
Function Type:
Extended Alarm Report – Date Based
Command Format:
Display:
<SOH>I11C00RRyymmddYYMMDDnnn
Computer:
<SOH>i11C00RRyymmddYYMMDDnnn
Notes:
1. RR -Report Type (Report Type should always be given. The rest of the parameters
are optional following the rules below.)
00=Active Alarm Report (for Active and Unacknowledged)
01=Alarm History Report – All Alarms
02=Alarm History Report – Priority Alarms
03=Alarm History Report – Non-Priority Alarms
2. yymmdd -Starting Date (If no start date is given or either Year, Month or Day
are zeroes, it assumes request is for most recent records. If
no start date is given, then the request is limited by the
Maximum Records (below))
Ranges are as follows:
yy=Year(01 – 99, for Years 2001-2099)
mm=Month (01 – 12, for Months January to December)
dd=Day (01 – 31, however, validity depends on Month)
3. YYMMDD -Ending Date (If no end date is given or either Year, Month or Day are
zeroes, it assumes request is for records starting from start
date as evaluated above, limited by the Maximum Records
(below)). Ranges are the same as for the Start Date fields.
4. nnn -Maximum Records – 1 - 999 (Absolute Maximum) (Decimal). (If no Maximum
Records is given or it’s zeroes, it assumes request is for
records starting from start date, ending by end date, and
limited by the Maximum Records Default of 100)
Typical Response Message, Display Format:
For an Active Alarm Report:
<SOH>
I11C0000
JAN 22, 1996 3:06 PM
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
Active Alarm Report
# Label Alarm Description Active Clear
T 12 PRODUCT 12 Probe Out 06-13-04 09:00 06-13-04 09:00
T 2 PRODUCT 2 Probe Out 06-13-04 09:00 06-13-04 09:00
<ETX>