Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
314
Function Code:
625
Version 1
Function Type:
Set Tank Sudden Loss Limit
Command Format:
Inquire:
Display:
<SOH>S625TTGGGGGG
<SOH>I625TT
Computer:
<SOH>s625TTFFFFFFFF
<SOH>i625TT
Notes:
1.
TT - Tank Number (Decimal, 00=all)
2.
GGGGGG - Sudden Loss Limit, Gallons (Decimal)
3.
FFFFFFFF - Sudden Loss Limit, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I625TT
JAN 22, 1996 3:18 PM
TANK SUDDEN LOSS LIMIT
TANK LABEL
GALLONS
1 REGULAR UNLEADED 100
<ETX>
Typical Response Message, Computer Format:
<SOH>i625TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
FFFFFFFF - Sudden Loss Limit, Gallons (ASCII Hex IEEE float)
4.
&& - Data Termination Flag
5.