Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
352
Function Code:
6C2
Version 1
Function Type:
Set Tank High Level Limit for Tall Tanks
Command Format:
Inquire:
Display:
<SOH>S6C2TTGGGGGGGGGGGG
<SOH>I6C2TT
Computer:
<SOH>s6C2TTFFFFFFFF
<SOH>i6C2TT
Notes:
1.
TT - Tank Number (Decimal, 00=all)
2.
GGGGGGGGGGGG - High Level Limit, Gallons (Decimal)
3.
FFFFFFFF - High Level Limit, Gallons (ASCII Hex IEEE float)
* Set Tank Maximum Volume Limit (628 or 6C8 cmd) must be set before the High Level
Limit.
Typical Response Message, Display Format:
<SOH>
I6C2TT
JAN 22, 1996 3:18 PM
TANK HIGH PRODUCT LIMIT
TANK LABEL
GALLONS PERCENT
1 REGULAR UNLEADED 770000 77
<ETX>
Typical Response Message, Computer Format:
<SOH>i6C2TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
FFFFFFFF - High Level Limit, Gallons (ASCII Hex IEEE float)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum