Function Code:
78E
Version 1
Function Type:
Set Pressure Line Leak 0.10 GPH Auto Test Enable
Command Format:
Inquire:
Display:
<SOH>S78EQQf
<SOH>I78EQQ
Computer:
<SOH>s78EQQf
<SOH>i78EQQ
Typical Response Message, Display Format:
<SOH>
I78EQQ
JAN 24, 1996 2:54 PM
PRESSURE LINE LEAK 0.10 GPH AUTO ENABLE
LINE 0.10 AUTO
Q 1:REGULAR UNLEADED ENABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i78EQQYYMMDDHHmmQQf...
QQf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pressure Line Leak sensor number (Decimal, 00=All)
3.
f - 0.10 GPH Test
0=Disabled
1=Enabled
4.
&& - Data Termination Flag
5.