
Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
385
Function Code:
P03
Version 1
Function Type:
Set Pump Mode
Command Format:
Inquire:
Display:
<SOH>SP03QQf
<SOH>IP03QQ
Computer:
<SOH>sP03QQf
<SOH>iP03QQ
Typical Response Message, Display Format:
<SOH>
IP03QQ
JAN 24, 1996 2:54 PM
PUMP MODE
PUMP MODE
Pm 1:REGULAR UNLEADED TLS Pump Control
<ETX>
Typical Response Message, Computer Format:
<SOH>iP03QQYYMMDDHHmmQQf...
QQf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
QQ - Pump number (Decimal, 00=All)
3.
f - Mode
1= TLS Pump Control (for PLLD and line manifold)
2= Pump Sense (pump sense only (as for CSLD 3 gph)
3= External Pump Control
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum