Serial Interface Manual
TLS4/TLS-450 Monitoring Systems
Part No. 577013-950, Revision L
118
Function Code:
2E3
Version 1
Function Type:
In-Tank Inventory History Report
Command Format:
Display:
<SOH>I2E3TTyymmddYYMMDDnnn
Computer:
<SOH>i2E3TTyymmddYYMMDDnnn
Notes:
1.
YYMMDDHHmm - Starting Date (000000 = no starting date)
2.
YYMMDD - Ending Date (000000 = no ending date)
3.
nnn - Maximum Records [001…999] (100 = default) (decimal)
Typical Response Message, Display Format:
<SOH>
I2E3TT
JAN 22, 1996 3:06 PM
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
Volume=GALLONS
Height=INCHES
INVENTORY HISTORY REPORT Temp=FAHRENHEIT
TANK 1: REGULAR UNLEADED
FUEL FUEL TC FUEL WATER WATER FUEL
DATE/TIME VOLUME VOLUME HEIGHT HEIGHT VOLUME TEMP
07/01/31 03:00 5329 5413 48.97 1.30 100 37.39
07/02/01 02:00 5329 5413 48.97 1.30 100 37.39
07/02/02 01:00 5329 5413 48.97 1.30 100 37.39
<ETX>
Typical Response Message, Computer Format:
<SOH>i2E3TTYYMMDDHHmmTTpnnnnssssYYMMDDHHmmNNFFFFFFFF...
ssssYYMMDDHHmmNNFFFFFFFF...
TTpnnnnssssYYMMDDHHmmNNFFFFFFFF...
ssssYYMMDDHHmmNNFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00=all)
3. p - Product Code (one ASCII character [20h-7Eh])
4. nnnn – Number of TimeStamped Records to follow (hex)
5. ssss - Tank Status Bits:
Bit 1 - (LSB) Delivery in Progress
Bit 2 - Leak Test in Progress
Bit 3 - Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 – Unused
6. YYMMDDHHmm - Timestamp
7. NN - Number of eight character Data Fields (hex)
8. FFFFFFFF - ASCII Hex IEEE floats:
1. Volume
2. TC Volume
3. Fuel Height
4. Water Height
5. Avg Fuel Temperature
6. Water Volume
7. Mass
8. Density
9. TC Density
9. && - Data Termination Flag
10. CCCC - Message Checksum