53
vacon
using macro mode and getting a quick start
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
6
6.3 Macro Mode Applications and Included Parameters
The tables below list the different applications and the Level 1 parameters included in the macro for that
application. The Factory Application macro is the core package (listed in Table 17); the other macros
include the Factory Application macro parameters as well as the ones listed in their respective tables
(Tables 18, 19, 20, 21, and 22). The macro mode applications are as follows:
•
Factory Application (Table 17)
•
Fan Application (Table 18)
•
Fan with PI Application (Table 19)
•
Pump Application (Table 20)
•
Pump with PI Application (Table 21)
•
Vector Application (Table 22)
Para. #
Parameter Name
Default
See Page
001
Model Number
Read-only
010
Last Fault
Read-only
102
Output Freq
Read-only
103
Output Voltage
Read-only
104
Output Current
Read-only
105
Drive Load
Read-only
106
Load Torque
Read-only
107
Drive Temp
Read-only
111
DC Bus Voltage
Read-only
201
Input Mode
Local Only
202
Rev Enable
Forward
301
Min Frequency
0.0 Hz
302
Max Frequency
60.0 Hz
303
Preset Freq 1
50 Hz
402
Accel Time 1
5.0 sec
403
Decel Time 1
5.0 sec
502
Voltage Boost
0.0%
610
Timed OL Select
In Duty 60sec
700
Vmet Config
Freq Out
705
Relay 1 Select
Drv Fault
706
Relay 2 Select
Drive Rdy
Table 17:Factory Application Macro
Para. #
Parameter Name
Default
See Page
203
Stop Key Remote
Coast
204
Ref Select
Vin1
205
Vin1 Config
0-10 V
206
Vin1 Offset
0.00%
207
Vin1 Span
100.00%
406
DC Inject Config
DC at Start
501
V/Hz Select
Fan Fixed
504
Skip Freq Band
0.2 Hz
505
Skip Freq 1
0.0 Hz
Table 18:Fan Application Macro
(Core Factory Application from Table 17, plus the following parameters)
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......