You may configure the drive to attempt to re-start a specified number of times after cer-
tain faults occur. Chapter 8 lists all faults and notes which ones may be reset automati-
cally.
The number of attempts at re-starting is set with parameter 608 (Restart Number). A val-
ue of 0 prevents the drive from attempting a re-start). The time duration that must elapse
between re-start attempts is set with parameter 609 (Restart Delay). The type of start to
be attempted is set with parameter 802 (Start Options); see page 83).
If the number of attempted re-starts is exceeded, the drive will trip with a fault and will
stop operating. Resetting the fault can result in instant starting. (See page 101 for more
information on faults and troubleshooting.)
Note that for 2-wire operation, the FWD or REV terminal must still be active for the drive
to attempt a re-start.
Also note that the counter for attempted re-starts will not reset to zero until ten minutes
after a successful re-start.
Two parameters in the Vacon 50X work together to configure how the motor timed over-
load operates: Parameter 510 (Rated Mtr FLA) and Parameter 610 (Timed OL Select).
Parameter 510 (Rated Mtr FLA) should be configured to the value on the nameplate of the
motor. This value is used in calculating the percentage of current at which the drive is op-
erating.
Set parameter 610 to one of the following data values to configure the desired overload
characteristic:
Options
Trip Time
Motor Type
Std Ind Shp
0 sec
Standard Induction
Std Ind 30s
30 sec
Standard Induction
Std Ind 60s
60 sec
Standard Induction
Std Ind 5mn
300 sec
Standard Induction
In Duty Shp
0 sec
Inverter Duty
In Duty 30s
30 sec
Inverter Duty
In Duty 60s
60 sec
Inverter Duty
In Duty 5mn
300 sec
Inverter Duty
Parameter 610 (Timed OL Select) determines the graph of Trip (Fault) Time vs. Percent
Current that is used by the Motor TOL functionality. This protective feature is speed-de-
608 Restart Number
609 Restart Delay
Default: 0
Default: 60 sec
P608 Range: 0–8
P609 Range: 0–60 sec
Level 2
WARNING
UNINTENDED EQUIPMENT ACTION
Ensure that automatic re-starting will not cause injury to
personnel or damage to equipment.
Failure to observe this instruction can result in serious injury
or equipment damage.
610 Timed OL Select
Default: In Duty 60sec
Range: Text string
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......