vacon 50x parameters
vacon
94
24-hour s358 (0)40 837 1150 • Email: [email protected]
7
method programmed in the control parameter. The bit patterns of the Seq Cntl X” parameters are
shown in Table 4:
Vacon 50X Sequencer Speed Selection
Table 5 gives more information on the speed selection options available in the Vacon 50X sequencer by
programming bits 0, 1, and 2 of each state’s control parameter. The options include any Preset Speed,
MaxFrequency, or allowing the reference to be determined in the normal Vacon 50X control path.
Vacon 50X Sequencer Ramping Selection
When the sequencer is active, the active ramp is no longer determined by parameter “Ramp Select.” The
user, however, does have the choice of using the main ramps (Accel Time 1/Decel Time1), or the alternate
ramps (Accel Time 2/Decel Time 2) for each independent state. This is determined by bit 3 of the control
parameter. If bit 3 is set to 1, then the alternate ramps are used (Accel Time 2/Decel Time 2).
Table 26:Seq Cntl Parameter, Bit Definition
10
9
8
7
6
5
4
3
2
1
0
Bit number
0
0
0
0
0
0
0
0
0
0
0
Program data
Bit
Description
10
9
Output Configuration:
00 - SeqOut-00
01 - SeqOut-01
10 - SeqOut-10
11 - SeqOut-11
8
7
Direction Selection:
00 - Stopped
01 - Forward
10 - Reverse
11 - DC Inject
6
5
4
State Duration:
000 - Time Base
001 - Pulse Count (Vin1)
010 - Low Volt Thres (Vin2)
011 - High Volt Thres (Vin2)
100 - Low Curr Thres (Cin)
101 - High Curr Thres (Cin)
110 - DI Compare
111 - Never Advance
3
Ramp Selection:
0 - Accel/Decel Time 1
1 - Accel/Decel Time 2
2
1
0
Speed Selection:
000 - Default Setpoint
001 - Preset Speed 1
010 - Preset Speed 2
011 - Preset Speed 3
100 - Preset Speed 4
101 - Preset Speed 5
110 - Preset Speed 6
111 - Max Frequency
Binary Value
Definition (Resulting Speed)
000
Speed selection as in normal Vacon 50X operation, as defined by parameters 204 (Ref Select)
and 201 (Input Mode).
001
Value of parameter Preset Speed 1 (303).
010
Value of parameter Preset Speed 2 (304).
011
Value of parameter Preset Speed 3 (305).
100
Value of parameter Preset Speed 4 (306).
101
Value of parameter Preset Speed 5 (307).
110
Value of parameter Preset Speed 6 (308).
111
Value of parameter Max Frequency (302)
Table 27:Speed Selection Options
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......