keypad operation and programming
vacon
40
24-hour s358 (0)40 837 1150 • Email: [email protected]
5
5.2 Keypad Operation
Parameter 201, Input Mode (see page 62), determines whether the Vacon 50X AC drive accepts its Run/
Stop and speed commands from the digital keypad or from the input terminals. Table 12 describes the
function of the keys in Operation mode.
Initiates forward run when pressed momentarily. If the drive is running in reverse
when FWD is pressed, it will decelerate to zero speed, change direction, and accelerate
to the set speed.
The green FWD designation in the key illuminates whenever a FWD command has been
given.
When both the FWD and REV lights are on, the DC braking function is active.
Initiates reverse run when pressed momentarily. If the drive is running in forward
when REV is pressed, it will decelerate to zero speed, change direction, and accelerate
to the set speed. The green REV in the key illuminates whenever a REV command has
been issued. When both the FWD and REV lights are on, the DC braking function is ac-
tive.
Causes a Ramp-to-Stop when pressed. Programmable to Coast-to-Stop by parameter
401, Ramp Select (page 67). The red STOP indicator in the key illuminates whenever a
STOP command has been given. If the drive has stopped because of a fault, this indica-
tor flashes to call attention to the display.
Press the Jog key to enter Jog mode. The green JOG indicator in the key illuminates
when the drive is in the JOG mode of operation. To jog the motor in either direction,
press either the FWD or REV (if REV is enabled in parameter 202). The motor will oper-
ate at the speed programmed in parameter 303. To exit Jog mode, press the JOG key
again.
When the drive is stopped, pressing this key increases the desired running speed.
When the drive is running, pressing this key increases the actual running speed in 0.1
Hz increments. Holding the SHIFT key while pressing the INC (UP arrow) key moves the
decimal place to the left with each press (0.1 Hz, 1.0 Hz, 10.0 Hz increments).
When the drive is stopped, pressing this key decreases the desired running speed.
When the drive is running, pressing the DEC (down arrow) key decreases the actual
running speed in 0.1 Hz increments. Holding the SHIFT key while pressing the DEC key
moves the decimal place to the right with each press (10.0 Hz, 1.0 Hz, 0.1 Hz incre-
ments).
NOTE: The operating speed for the drive is stored on Power Down.
Pressing this key while a parameter is displayed allows that parameter to have its val-
ue changed by use of the INC and DEC (up and down arrow) keys. The P indicator flash-
es to show that the parameter can be programmed. See also the descriptions for the
INC and DEC keys above to see how they work with the SHIFT key.
The ENTER key has no function when the drive is running or stopped. ENTER can be
used to store the speed command so that it is saved through a power-down. To enable
this function, see the description for parameter 802 (Start Options) on page 83.
Table 12:Function of Keys in Operation Mode (Vacon 50X Running or Stopped)
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......