vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
0-20mA 50
0 to 20 mA current signal with 50 Ohm load
0-20mA 50I
0 to 20 mA current signal with 50 Ohm load Inverted
When the signal range is inverted (that is, the minimum input corresponds to the maxi-
mum output, while the maximum input corresponds to the minimum output).
Parameter 209, Cin Offset, configures the offset for analog input Cin expressed as a per-
centage of the maximum value of the input signal. Note that if the input signal drops be-
low the offset value or if the input signal is lost (if no offset is configured), a fault will be
generated.
Parameter 210, Cin Span, is used to alter the range of the input signal for analog input
Cin. For example, if parameter 208 (Cin Config) selects the 0 to 20 mA input signal, setting
this parameter to 50% reduces it to 0 to 10 mA.
Parameter 211, Vin2 Config, selects the type of signal for analog input Vin2. Parameters
212 (Vin2 Offset) and 213 (Vin2 Span) may be used to customize the selected range. The
following data values may be assigned to this parameter:
Parameter Value
Description
0-10V
0–10 Vdc signal
0-10V Brk W
0–10 Vdc signal with broken wire detection for speed pot op-
eration
0-10V I
0–10 Vdc signal inverted
0-10V Bipol
0–10 Vdc signal (5 Vdc is stop with 0 Vdc Full REV and 10 Vdc
Full FWD
0-5V
0–5 Vdc signal
0-5V I
0–5 Vdc signal inverted
Parameter 212, Vin2 Offset, configures the offset for analog input Vin2 expressed as a
percentage of the maximum value of the input signal. Note that if the input signal drops
below the offset value or if the input signal is lost (if no offset is configured), a fault will
be generated.
Parameter 213, Vin2 Span, is used to alter the range of the input signal for analog input
Vin2. For example, if parameter 211 (Vin2 Config) selects the 0 to 10 Vdc input signal, set-
ting this parameter to 50% reduces it to 0 to 5 Vdc.
209 Cin Offset
Default = 0.0%
Range: 0.0–100.0%
Level 2
210 Cin Span
Default = 100.0%
Range: 10.0–200.0%
Level 2
211 Vin2 Config
Default = 0-10 V
Range: Text string
Level 2
212 Vin2 Offset
Default = 0.0%
Range: 0.0–100.0%
Level 2
213 Vin2 Span
Default = 100%
Range: 10.0–200.0%
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......