4.6 Reducing Current Surges and Voltage Transients
Inrush currents to coils of magnetic contactors, relays, and solenoids associated with or near the
drive can induce high current spikes in the power and control wiring, causing faulty operation. If this
occurs, a snubber network consisting of a series resistor and capacitor for AC loads, or a freewheeling
or flyback diode for DC loads, can be placed across the relay coil to prevent this condition.
The following component values should be used for 115 VAC or 230 VAC relays or solenoids.
Figure 18: Connection Diagram for AC and DC Relay Coils and Solenoids
For magnetic contactors, relays, and solenoids energized from a DC source, use a free-wheeling diode of
the high-speed, fast-recovery type. Connect the diode across the coil as shown above in Figure 18. The
diode current and voltage should be selected using the following formulae:
For Main Circuit Contactors and Solenoids
C = 0.2 MFD, 500 VDC R = 500 5 Watts
For Auxiliary Control Circuit Relays
C = 0.1 MFD, 500 VDC R = 200 2 Watts
RC Type
Snubber
AC
Coil
Coil
DC
+
-
Freewheeling
Diode
Diode Current Rating (A)
Coil Capacity (VA)
Rated Voltage of Coil (V)
Rated Voltage of Coil (V) x 2
Diode Voltage Rating
=
=
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......