4.5 Terminals Found on the Vacon 50X Control Board
4.5.1 Description of the Control Terminals
Figure 12 shows the control terminals found on the I/O board of the Vacon 50X AC drive. See page 9 for
specifications. Table 10 on page 33 describes the control terminals.
The drive’s control terminals are referenced to earth ground through a resistor / capacitor network. Use
caution when connecting analog signals not referenced to earth ground, especially if the communications
port (J3) is being used. The J3 port includes a common reference that can be connected to earth ground
through the host PLC or computer.
Figure 12: Vacon 50X Control Terminals
Terminal
Description
Vmet
Analog output 1, which is a dedicated voltage output.
The default signal range is from 0 to 10 Vdc (5 mA maximum). It is proportional to the variable
configured by parameter 700 (Vmet Config) (see page 79). It may be calibrated while the drive
is running via parameter 701 (Vmet Span) (see page 79).
Imet
Analog output 2, which is a dedicated current output.
The default signal ranges from 0 to 20 mAdc (50 to 500
Ω
). It is proportional to the variable
configured by parameter 702 (Imet Config) (see page 80). It may be calibrated while the drive is
running via parameters 704 (Imet Offset) and 703 (Imet Span) (see page 80).
Vin1
Analog Input 1, which is used to provide speed references.
The default input signal is 0 to 10 Vdc (the type of input signal is selected with parameter 205
(Vin1 Config); see page 64). Parameters 206 (Vin1 Offset) and 207 (Vin1 Span) may be used to
offset the starting value of the range and the size of the range, respectively; see page 64 for
more information.
If a 0 to 20 mAdc input signal is configured, the burden is 250 ohm. If a 0 to 10 Vdc input
signal is configured, the input impedance is 475 kohm.
A potentiometer with a range of 1 to 2 kohm is suggested for this input.
+10
This terminal is a +10 Vdc source for customer-supplied potentiometers. The maximum load on
this supply cannot exceed 10 mAdc.
Table 10:Description of Vacon 50X Control Terminals
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......