This parameter configures the analog signal that will be applied to the Imet output pin.
The following data values may be assigned to this parameter:
This parameter sets the span of the Imet analog output.
This parameter sets the offset of the Imet analog output.
This parameter configures what condition will cause relays R1and R2 to activate. The fol-
lowing values may be assigned:
Parameter Value
Description
Drv Ready
The drive is ready. (The relay will be open in Fault and Low
Voltage conditions.)
Drv Fault
A fault occurs. (If automatic fault reset and re-start is en-
abled, only faults that cannot be reset will activate the relay.
The relay will also activate for faults that can be reset when
the number of restart attempts exceeds the value set in pa-
rameter 608 (Restart Number).)
Drive Run
The drive has received a direction command.
Running FWD
The motor is running Forward and the output frequency is
above 0.5 Hz.
702 Imet Config
Default: Drive Load
Range: Text string
Level 2
Parameter Value
Description
Range Limit
Freq Out
Output frequency of the
drive
Parameter max freq.
Voltage Out
Voltage being supplied to
the motor
Rated motor voltage
Current Out
Current being supplied to
the motor
200% of drive rating
Drive Load
Calculated percentage of
drive rating
200% of drive rating
Drive Temp
Calculation of total drive
temp rating
100% of unit temp rating
Stator Freq
Commanded frequency
100% of input config
Power Out
Calculated power output of
drive
250% of drive rating
PI Fback
Allows the analog output to
produce a signal in propor-
tion to the PI feedback re-
ceived
703 Imet Span
Default: 100%
Range: 0.0–200.0%
Level 2
704 Imet Offset
Default: 0.0%
Range: 0.0–90.0%
Level 2
705 Relay 1 Select
706 Relay 2 Select
707 DO1 Select
708 DO2 Select
Default: Drv Ready
Default: Drive Run
Default: Drive Ready
Default: At Speed
Range for Parameters 705–708: Text string
Levels 1, 2 for Parameters 705–706
Level 2 for Parameters 707–708
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......