keypad operation and programming
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
Table 16 shows Vacon 50X keypad warning messages that may appear during operation:
FWD Decel
The drive is spinning the motor in the forward direction and the speed of the motor is de-
creasing.
REV Decel
The drive is spinning the motor in the reverse direction and the speed of the motor is de-
creasing.
Jog FWD
The drive is jogging in the forward direction.
Jog REV
The drive is jogging in the reverse direction.
FWD At Spd
The drive is spinning the motor in the forward direction and the speed of the motor is at the
reference frequency.
REV At Spd
The drive is spinning the motor in the reverse direction and the speed of the motor is at the
reference frequency.
Zero Speed
The drive has an active run signal but the motor is not spinning because the reference
speed to the drive must be 0.0 Hz.
DC Inject
The drive is injecting DC voltage into the motor.
Faulted
The drive is faulted.
Reset-Flt
The drive is faulted, but has the possibility of being automatically reset.
LS Lockout
Line-Start Lockout functionality has become active. This means there was an active run
signal during power-up or when a fault was reset. This run signal must be removed before
the Line-Start Lockout functionality will be removed.
Catch Fly
The Catch on the Fly functionality is actively searching for the motor frequency.
Forward
The drive is running forward without accelerating, decelerating or residing at the reference
frequency. This means that something is keeping the drive from the reference frequency
(for example, Current Limit).
Reverse
The drive is running in reverse without accelerating, decelerating or residing at the refer-
ence frequency. This means that something is keeping the drive from the reference fre-
quency (for example, Current Limit).
Not Enabled
The drive is not allowed to run either because the digital input enable is not active or be-
cause ARCTIC mode has shut down the run operation.
Volt Range
The drive has not met the input voltage requirements that it needs to be able to run. In other
words,the Bus Voltage of the drive is either too low or too high.
Low Voltage The drive has reached an undervoltage state.
Kpd Stop
A stop command was given from the keypad when the keypad was not the active control
source. To remove this condition, the run signal to the drive must be removed.
Message
Meaning
DB Active
The DB Resistor is being actively pulsed.
Curr Limit
The drive is operating in current limit.
HS Fan Err
Either the heatsink fan should be on and is off, or vice-versa.
Addr XXX
This is the node address of the drive when it receives a valid message through the IR
port
address to another node. The XXX will be replaced with the node address.
High Temp
The temperature of either the heatsink or the control board is nearing a high tempera-
ture limit that will fault the drive.
Low Temp
The temperature of either the heatsink or the control board is nearing a low tempera-
ture limit that will fault the drive.
Vac Imblnce
Either the drive has lost an input phase or the input voltage is unbalanced more than
2%.
Power Supp
A power supply short occurred.
Table 16:Keypad Warnings
Table 15:Keypad Status States
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......