93
vacon
vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
Keypad Control (Activation) of the Vacon 50X Program Sequencer
When activating or controlling the Vacon 50X Program Sequencer from the keypad, pressing the FWD key
commands the drive to cycle through the programmed states of the sequencer one time only (oneshot
operation). One-shot operation will run the sequencer until state 9 is reached, or until any state that is
not changed from the default is reached.
Pressing the SHIFT and FWD keys simultaneously causes the programmed sequence to repeat until the
Stop key is pressed (continuous operation). In continuous mode, the sequencer runs until state 9 or any
state that is not changed from the default is reached; it then jumps back to state 1.
Note that the REV key has no function in the sequencer mode.
Terminal Control of the Vacon 50X Program Sequencer
When activating or controlling the Vacon 50X Program Sequencer from terminals, continuous and one-
shot operation is determined by whether the drive is wired for 2-wire or 3-wire control. If the terminal is
set up for 2-wire control, the sequencer operates in continuous mode (R/J terminal inactive). This will run
the sequencer until the Forward command is removed. If the terminal is set up for 3-wire control, the se-
quencer runs one cycle when the FWD terminal is activated.
Note that the REV terminal has no function in sequencer mode.
Vacon 50X Sequencer Dwell Functionality
The Vacon 50X sequencer has the capability to dwell, or pause, in a state and disregard any command to
advance to the next state. This can be done in two different ways, and both methods can be used at the
same time.
If the sequencer is actively running and the Enter key is pressed from the Operate screen of the Vacon
50X keypad, the sequencer will dwell in the current state (it will never advance to the next state). While
the sequencer is dwelling, a warning of “Seq Dwell” will flash on the Operate screen. To leave the dwell
state, press the Enter key again from the Operate screen.
The sequencer Dwell mode can also be entered by programming a digital input to “Seq Dwell.” The se-
quencer will then dwell in the current state, for as long as the digital input is active.
Vacon 50X Sequencer Advance Functionality
The sequencer has the ability to allow the user to advance to the next state without satisfying the condi-
tions programmed to advance. To do this, program a digital input to “Seq Advance.” When a digital input
program to this option changes from inactive to active, a running sequencer will advance one state. This
feature is useful when debugging a sequence with long time intervals.
7.4.3 Sequencer State Configuration Overview
Each state of the program sequencer is defined by five characteristics:
•
Direction in which the drive will operate
•
Speed at which the drive will operate
•
Ramp selection of the drive
•
Output configuration (relays and digital outputs) of the drive
•
How the sequencer advances to the next state.
These five characteristics are configured by two parameters for each state. These parameters are
named “Seq Cntl X” and “Seq Count X,” where X represents the state number of the sequencer. The “Seq
Cntl X” parameter is a binary parameter that sets each of the five characteristics listed above. “Seq
Count X” configures the threshold that the sequencer will use in determining when to advance by the
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......