pendent to handle standard induction motors whose cooling is limited by the shaft-
mounted fan. Blower-cooled motors and most inverter-duty motors do not have this lim-
itation.
This parameter operates as a percentage of the longest ramp time. This time then de-
fines the amount of time a deceleration to stop can take without causing a “Regen Time-
out” fault. For example, if “Decel Time 1” is 5.0 seconds, “Decel Time 2” is 10.0 seconds,
and “Max Regen Ramp” is 300%, a deceleration to stop that takes more than 30 seconds
will cause a “Regen Timeout” fault in the drive.
Both of these parameters can be used to resolve stability problems if they occur. Use Pa-
rameter 615 if the load has significant inertia with respect to the motor itself.
This parameter configures the analog signal that will be applied to the Vmet output pin.
The following data values may be assigned to this parameter:
This parameter sets the span of the Vmet analog output.
613 Max Regen Ramp
Default: 300%
Range: 100–1000%
Level 2
614 Stability Gain
Default: Model dependent
Range: 0–10
Level 2
615 Stability Rate
Default: Model dependent
Range: 0–1000
Level 2
700 Vmet Config
Default: Freq Out
Range: Text string
Levels 1, 2
Parameter Value
Description
Range Limit
Freq Out
Output frequency of the
drive
Parameter max freq.
Voltage Out
Voltage being supplied to
the motor
Rated motor voltage
Current Out
Current being supplied to
the motor
200% of drive rating
Drive Load
Calculated percentage of
drive rating
200% of drive rating
Drive Temp
Calculation of total drive
temp rating
100% of unit temp rating
Stator Freq
Commanded frequency
100% of input config
Power Out
Calculated power output
of drive
250% of drive rating
PI Fback
Allows the analog output
to produce a signal in pro-
portion to the PI feedback
received
100% of feedback signal
701 Vmet Span
Default: 100%
Range: 0.0–200.0%
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......