This parameter configures the time constant of a first-order filter of the Vin1 analog in-
put. When this parameter is a value of 0 ms there is no software filtering of the analog
input. Note that long filter times will create a delay in the drive response to signal chang-
es.
This parameter configures the time constant of a first-order filter of the Cin analog input.
When this parameter is a value of 0 ms there is no software filtering of the analog input.
Note that long filter times will create a delay in the drive response to signal changes.
This parameter configures the time constant of a first-order filter of the Vin2 analog in-
put. When this parameter is a value of 0 ms there is no software filtering of the analog
input. Note that long filter times will create a delay in the drive response to signal chang-
es.
This parameter enables or disables trimming of the drive reference by an analog input
and selects which analog input will perform the trimming function.
Speed Ref. = Main ref.+(Trim % Factor) x value of parameter 217 x Max Frequency
100%
Parameter Value
Description
Disabled
No trimming of drive reference
Vin1
Value of Vin1 will be used in the calculation above
Vin2
Value of Vin2 will be used in the calculation above
Cin
Value of Cin will be used in the calculation above
Fxd Trim %
Value of Fxd Trim % will be used
Drive Ref. = Drive ref.+ (Trim % Factor) x Max Frequency
100%
Note that setting a parameter for a Bipolar input value allows trimming both positive and
negative around the reference value.
This parameter determines the percentage of the analog input signal selected in Param-
eter 217, Trim Ref Enable, that will affect the reference signal.
This parameter allows for the control of the drive’s response to a 4-20mA input on either
the Vin1 or Cin input terminals when the input drops below approximately 3mA. The de-
fault value is No Fault. The options for this parameter are:
Retain Spd
Hold the last operating speed
Preset Spd2
Go to the speed programmed at address 304
Fault
Drive faults with an F22 Reference Loss indication
No Fault
Drive does NOT fault; operating frequency drops to the limit set at Parameter
301, Min Frequency
214 Vin1 Filter Time
Default = 20 ms
Range: 0–1000 ms
Level 2
215 Cin Filter Time
Default = 20 ms
Range: 0–1000 ms
Level 2
216 Vin2 Filter Time
Default = 20 ms
Range: 0–1000 ms
Level 2
217 Trim Ref Enable
Default =
Disabled
Range: Text string
Level 2
218 Trim % Factor
Default = 0.0%
Range: –100.0 to 100.0%
Level 2
222 Ref Loss Fault
Default =
Disabled
Range: Text string
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......