connections
vacon
24
24-hour s358 (0)40 837 1150 • Email: [email protected]
4
3.
Wire gauge must be selected based on 125% of the continuous input current rating
of the drive. Wire gauge must be selected from wire tables for 75 °C insulation rat-
ing, and must be of copper construction. The 230 V 5.5 and 11 kW models, and the
460 V 22 kW models require 90 °C wire to meet UL requirements. See Chapter 2 for
the continuous output ratings for the drive.
4.
Grounding must be in accordance with VDE, NEC and CEC. If multiple Vacon 50X
drives are installed near each other, each must be connected to ground. A central
earthing point should be used for interference suppression (e.g. equipotential
bonding strip or centrally at an interference suppression filter). The earthing lines
are routed to the respective terminals radially from this point. Conductor loops of
the earthing lines are impermissible and can lead to unnecessary interference.
See Table 4 below for a summary of power terminal wiring specifications.
NOTE: Wire type not specified by the manufacturer. Some types of wire may not fit within the
constraints of the conduit entry and bend radius inside the drive.
4.1.3 Considerations for Control Wiring
Control wiring refers to the wires connected to the control terminal strip. Select control wiring as follows:
1.
Shielded wire is recommended to prevent electrical noise interference from caus-
ing improper operation or nuisance tripping.
2.
Use only VDE, UL or CUL recognized wire.
3.
Wire voltage rating must be at least 300 V for 230 Vac systems. It must be at least
600 V for 460 Vac systems.
See Table 5 below for a summary of power terminal control wiring specifications.
Vacon 50X Size /
Models
Specifications
Size 0
1.36 Nm (12 in-lbs) nominal torque or
1.47 Nm (13 in-lbs) maximum torque
1.5–4 mm
2
(11–15 awg wire)
Size 1
1.8 Nm (16 in-lbs) nominal torque or
2.0 Nm (18 in-lbs) maximum torque
1.5–10 mm
2
(7–15 awg wire)
Size 2
3.4 Nm (30 in-lbs) nominal torque
10–16 mm
2
(5–7 awg wire)
Size 3
4.0 Nm (35 in-lbs) nominal torque
25 mm
2
(3 awg wire)
Size 4
7.3 Nm (64 in-lbs) nominal torque
25 mm
2
(3 awg wire max)
Size 5
14.9 Nm (131 in-lbs) nominal torque
120 mm
2
(250MCM wire max)
Table 4:Vacon 50X Power Terminal Wiring Specifications
Vacon 50X Size / Models
Specifications
All Sizes / Models
0.5 Nm (4.4 in-lbs) maximum torque
0.2–4 mm
2
(12–24 awg wire)
Table 5:Vacon 50X Control Wiring Specifications
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......