vacon 50x parameters
vacon
96
24-hour s358 (0)40 837 1150 • Email: [email protected]
7
7.4.4 Sequencer Status Indicators
When the sequencer is enabled, the control path indication field on the keypad will indicate SQx, where x
represents the active state of the sequencer. A sample operate screen (where the sequencer is in state
1) is shown below:
Bits 4, 5, 6
of Seq Cntl
Description of Seq Count Function
000
Time Base – The current sequencer state will last for a time interval equal to the number “Seq
Count X” multiplied by the time base configured in the Seq Appl parameter.
Seq Appl Setting
Time to Advance
Maximum Sequence Time
1 sec Base
(1 sec) * (Seq Count X)
18.2 hours
.1 sec Base
(0.1 sec) * (Seq Count X)
1.82 hours
0.01 sec Base
(0.01 sec) * (Seq Count X)
10.92 minutes
001
Pulse Count – The current sequencer state will last until the number of pulses programmed into
“Seq Count X” is detected on terminal Vin1.
010
Low Analog Voltage Threshold – The active sequencer state lasts until the voltage signal applied
to terminal Vin2 is < a value programmed into “Seq Count X.” The value programmed into “Seq
Count X” should be the percentage of input after span and offset are applied (where 100.00% =
10000).
Note: The % of analog input after span and offset can be read in parameter 912, Vin2 Status.
011
High Analog Voltage Threshold – The active sequencer state lasts until the voltage signal applied
to terminal Vin2 is > a value programmed into “Seq Count X.” The value programmed into “Seq
Count X” should be the percentage of input after span and offset are applied (where 100.00% =
10000).
Note: The % of analog input after span and offset can be read in parameter 912, Vin2 Status.
100
Low Analog Current Threshold – The active sequencer state lasts until the current signal applied
to Cin terminals is < a value programmed into “Seq Count X.” The value programmed into “Seq
Count X” should be the percentage of input after span and offset are applied (where 100.00% =
10000).
Note: The % of analog input after span and offset can be read in parameter 911, Cin Status.
101
High Analog Current Threshold – The active sequencer state lasts until the current signal applied
to Cin terminals is > a value programmed into “Seq Count X.” The value programmed into “Seq
Count X” should be the percentage of input after span and offset are applied (where 100.00% =
10000).
Note: The % of analog input after span and offset can be read in parameter 911, Cin Status.
110
Digital Comparison – The active sequencer state lasts until the binary value of digital inputs
configured to Seq1, Seq2, and Seq3 is equal to the value programmed into “Seq Count X.”
Note: For this option to work, “DIx Configure” parameters must be set to “Seq1,” “Seq2,” and
“Seq3.”
Seq Count
Digital Input Terminals
Description
Seq1
Seq2
Seq3
0
0
0
0
No input active
1
1
0
0
Seq1 active
2
0
1
0
Seq2 active
3
1
1
0
Seq1 & Seq2 active
4
0
0
1
Seq3 active
5
1
0
1
Seq1 & Seq3 active
6
0
1
1
Seq2 & Seq3 active
7
1
1
1
Seq1, Seq2, Seq3 active
111
The sequencer will never advance if this option is selected.
Table 28:Seq Count Definition Based on Cntl Parameter Configuration
S
Q
1
:
S
t
o
p
p
e
d
0
.
0
H
z
+
0
%
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......