10. Fundamentals of PI Control
10.1 Introduction
The Vacon 50X AC drive has a built-in PI (Proportional-Integral) Controller that makes it possible to con-
trol a process by adjusting motor speed using a reference input and a feedback input. When the drive is
configured to operate with feedback from a transducer, the Vacon 50X AC drive essentially ceases to be
a frequency controller and instead becomes a process controller.
Several Vacon 50X parameters are specifically designed for PI control. These include:
•
490 (Appl Macro)
•
850 (PI Configure)
•
851 (PI Feedback)
•
852 (PI Prop Gain)
•
853 (PI Int Gain)
•
854 (PI Feed Gain)
•
855 (PI Error 1)
•
856 (PI Error 2)
•
857 (PI High Corr)
•
858 (PI Low Corr)
The function performed by each of these parameters is described in the following section. Figure 22 on
page 108 provides a flowchart of PI control and shows the interaction of these parameters.
10.2 Configuration of PI Control Parameters
This section discusses the parameters used for PI control and provides advice on how best to configure
these parameters for your particular application.
10.2.1 Parameter 490 (Appl Macro)
Parameter 490 (Appl Macro) is used to active the PI mode for either a Fan with PI or Pump with PI appli-
cation.
10.2.2 Parameter 857 (PI High Corr) and 858 (PI Low Corr)
These two parameters define the correction limits for the drive’s response to a change in, or loss of, the
feedback signal.
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......