vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
This parameter (Special Program Number) provides a way of enabling hidden functions
in the drive and storing parameters to the customer set.
Data Value
Special Function Configured
0
Standard program
1
Reset all parameters to factory default values (display =
SETP).
2
Store customer parameter values (display = STOC).
3
Load customer parameter values (display = SETC).
4
Swap active parameters with customer stored settings.
10
Reset Total Run Time, parameter 108.
The Start Options parameter configures the Line Start Lockout functionality of the drive.
All data values ending with “2” allow the user to press the Enter key to store the customer
speed reference value on the keypad. You must press and hold the Enter key for two sec-
onds to save the speed command. The following data values may be assigned to this pa-
rameter:
Data Value
Description
LS Lockout
(Line Start Lockout). If maintained contact run operators are
used, they must be opened and then re-closed for the drive to
start after AC power is applied.
AutoStart
When AC power is applied, if a Run command is present
through the terminal strip, the drive will start.
LSL w/FLY
This setting has both LS Lockout and Catch on the Fly enabled
at the same time.
Auto w/FLY
This setting has both Auto-Start and Catch on the Fly enabled
at the same time.
LS Lockout2
(Line Start Lockout). If maintained contact run operators are
used, they must be opened and then re-closed for the drive to
start after AC power is applied.
AutoStart2
When AC power is applied, if a Run command is present
through the terminal strip, the drive will start.
LSL w/FLY 2
This setting has both LS Lockout and Catch on the Fly enabled
at the same time.
Auto w/FLY2
This setting has both Auto-Start and Catch on the Fly enabled
at the same time.
The PWM Carrier Frequency parameter sets the carrier frequency of the Pulse-Width
Modulation (PWM) waveform supplied to the motor. Low carrier frequencies provide bet-
ter low-end torque, but produce some audible noise from the motor. Higher carrier fre-
quencies produce less audible noise, but cause more heating in the drive and motor.
801 Program Number
Default: 0
Range: 0–9999
Level 2, Macro
802 Start Options
Default: LS Lockout
Range: Text string
Level 2
803 PWM Frequency
Default: 3.0 kHz
Range: 0.6–16.0 kHz
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......