Parameter 301, Minimum Frequency, configures the minimum frequency output of the
drive. This parameter governs the minimum frequency when operating from the keypad
or from an analog input. The preset speeds can be set lower than the minimum frequency
in parameter 301.
Parameter 302, the Maximum Frequency parameter, configures the maximum frequency output of the drive.
These parameters configure six preset speeds in addition to the normal reference speed
of the drive (as defined by parameters 201 (Input Mode) and 204 (Ref Select) and the max-
imum frequency of the drive (as set with parameter 302, Max Frequency). Thus, in effect,
you may choose to operate the drive at up to eight different speeds.
The eight speeds are selected by a combination of three digital inputs (PS1, PS2, PS3). A
wiring scheme for utilizing preset speeds is provided on page 24 along with a truth table
showing what combination of inputs results in the selection of which speeds.
Note that parameter Parameter 303 (Preset Freq1) also serves as the reference frequen-
cy for jogging.
This parameter sets the point where the drive no longer attempts to spin the motor. The
range of this parameter is 0.0–5.0 Hz. When the parameter is configured to a value of 0.0
Hz, the drive will operate with no Cut-off Frequency. If the function is enabled, the drive
will be able to ramp up through the cut-off frequency range, as in normal operation. If the
speed command falls below the cut-off frequency, the drive stops “gating” the outputs
and coasts down to zero speed. The keypad display will indicate Zero Speed, and the For-
ward or Reverse LED will be lit depending on the command. When the reference returns
to a value greater than the cut-off frequency, the drive will ramp from 0.0 Hz to the ref-
erence frequency.
The Ramp Select parameter configures when the alternate ramps of the drive will be ac-
tive and whether the drive ramps to stop, or coasts to stop. The following data values may
be assigned to this parameter:
301 Min Frequency
Default = 0.0%
Range: 0.0–Max Freq
Level 1
302 Max Frequency
Default: 50 Hz
Range: 0.0–400.0 Hz
Level 1
303 Preset Freq 1 (Jog Ref)
304 Preset Freq 2
305 Preset Freq 3
306 Preset Freq 4
307 Preset Freq 5
308 Preset Freq 6
Default: 5 Hz
Default: 10 Hz
Default: 20 Hz
Default: 30 Hz
Default: 40 Hz
Default: 50 Hz
Range: Min–Max Freq
Levels 1, 2 for 303
Level 2 for 304–308
309 Cut-Off Freq
Default = 0.0 Hz
Range: 0.0–5.0 Hz
Level 2
401 Ramp Select
Default: ART-DI
Range: Text string
Level 2
Parameter Value
Type of Ramp
Ramp Configured by:
ART-DI
Ramp-to-Stop
402 (Accel Time 1) and 403 (Decel Time 1)
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......