vacon 50x parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
Parameter 055, 2nd Fault, lists the fault that occurred 3 before the last.
For more information, refer to Chapter 8, “Troubleshooting”, beginning on page 101.
Parameter 070, 1st Fault, lists the fault that occurred 4 before the last.
For more information, refer to Chapter 8, “Troubleshooting”, beginning on page 101.
Parameter 102, the Output Frequency parameter, shows the frequency being applied to
the motor connected to the drive (ramp).
Parameter 103, the Output Voltage parameter, displays the output voltage of the drive.
Parameter 104, the Output Current parameter, displays the output current of the drive.
Parameter 105, the Drive Load parameter, shows the percentage torque of the drive
when operating below the knee frequency. It displays Load Torque if the frequency is be-
low FKNEE, and displays Power if above FKNEE.
The output current is measured with the motor power factor applied to an accuracy of
±20%. The parameter value is positive when the motor is pulling a load (“motoring mode”)
and negative when being pulled by a load (“regenerative mode”).
Parameter 106, the Load Torque parameter, displays the load torque of the drive.
Parameter 107, the Drive Temp parameter, shows the actual temperature of the drive’s
heatsink. The drive will fault when the internal temperature reaches 85 °C.
Parameter 108, Total Run Time, is a resettable timer for drive operation. To reset the tim-
er, enter 10 in parameter 801, Program Number.
055 2nd Fault
Read-Only
Range: Text string
Level 2
070 1st Fault
Read-Only
Range: 0–65535
Level 2
102 Output Freq
Read-Only
Range: 0.0–400.0 Hz
Levels 1, 2
103 Output Voltage
Read-Only
Range: 0–600 V
Levels 1, 2
104 Output Current
Read-Only
Range: 0.0–200.0 A
Levels 1, 2
105 Drive Load
Read-Only
Range: –200.0 to 200.0%
Levels 1, 2
106 Load Torque
Read-Only
Range: –200.0...200.0%
Levels 1, 2
107 Drive Temp
Read-Only
Range: –20.0...200.0 °C
Levels 1, 2
108 Total Run Time
Read-Only
Range: 0.0–6553.5 h
Level 2
Содержание 50X
Страница 1: ......
Страница 5: ...introduction vacon 4 24 hour support 358 0 40 837 1150 Email vacon vacon com 1 ...
Страница 23: ...receiving and installation vacon 22 24 hour support 358 0 40 837 1150 Email vacon vacon com 3 ...
Страница 30: ...29 vacon connections Tel 358 0 201 2121 Fax 358 0 201 212205 4 Figure 11 Power Terminals Size 4 and 5 ...
Страница 39: ...connections vacon 38 24 hour support 358 0 40 837 1150 Email vacon vacon com 4 ...
Страница 49: ...keypad operation and programming vacon 48 24 hour support 358 0 40 837 1150 Email vacon vacon com 5 ...
Страница 59: ...using macro mode and getting a quick start vacon 58 24 hour support 358 0 40 837 1150 Email vacon vacon com 6 ...
Страница 101: ...vacon 50x parameters vacon 100 24 hour support 358 0 40 837 1150 Email vacon vacon com 7 ...
Страница 107: ...hexadecimal to binary conversion vacon 106 24 hour support 358 0 40 837 1150 Email vacon vacon com 9 ...
Страница 113: ...eu declaration of conformity vacon 112 24 hour support 358 0 40 837 1150 Email vacon vacon com 11 ...
Страница 131: ...summary of vacon 50x parameters vacon 130 24 hour support 358 0 40 837 1150 Email vacon vacon com 12 ...
Страница 132: ......