UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
55
External exchanger electric heater parameters (folder PAr/HE)
Parameters for external circuit heaters can be viewed and configured in folders HE: External circuit electric heater parameters (see User
Interface and Parameters chapters).
The heaters are used for the antifreeze function.
•
They are active only when the relative parameter enabling them HE00=1 (see table).
•
In Std-by the heaters can be enabled by configuring HE01 (see table).
•
The regulation probe can be selected in parameter HE02
•
The setpoint can be set in parameter HE03.
Heaters
Parameter
Description
Value
0
1
External
exchanger
HE00
Enable external exchanger heaters for antifreeze
Heaters disabled
Heaters enabled
External
exchanger
(Standby
mode)
HE01
Enable external exchanger heater regulator in
standby for antifreeze
Heaters disabled
Heaters enabled
External
exchanger
HE02
Select probe to regulate external exchanger heaters
during antifreeze
External exchanger
inlet water
temperature
External exchanger
outlet water
temperature
Heaters
Parameter
Description
Value
External
exchanger
HE03
External exchanger heater switch on setpoint for
antifreeze
Range defined in parameters
HE04..HE05
Hysteresis defined in parameter HE06
External exchanger heaters
Regulation is performed as shown in the figure:
HEAT
HE03
External exchanger heater switch on setpoint for antifreeze
HE06
External exchanger heater regulator hysteresis for antifreeze
AIn temp.
AIn probe temperature
See HE02
Heaters
Heater state
OFF
Heaters
Temp AIn
HE06
ON
HE03