UST500 CONTROL BOARD
68 06MC0074@00B0100
14/04/2010
Analogue alarms
NOTES
(NOTE 1) If no. interventions = 0, when the first event occurs there is a manual reset alarm.
(NOTE 2) Alarm bypass is active in heating mode only.
Table of Alarms
The alarm signal consists of a code, the format being “Ernn” (nn is a 2-figure number identifying the type of alarm, eg: Er00, Er25, Er39….).
When more than one alarm occurs at the same time, the one with the lowest number will be shown first; (e.g. simultaneous alarms Er00 and
Er01). Er00 will be shown alternating between the display and the main screen.
If the measurement on the main display is incorrect, in the event of an alarm, the alternate alarm code will alternate with “----“.
All possible alarms are listed in the table below with their respective codes and the relative utilities blocked:
Alarm table key
column
Alarm
code
N.B: codes are listed in increasing order (Er00, Er01) and
some numbers are “skipped” (Er02 does not exist).
Name of
alarm
Notes
CMP 1/2
Compressor 1/power step 2
PUMP 1/2
Pump 1/2
Alarm
D
Digital
A
Analogue
See digital alarms table
Reset
AUTO
Automatic
UTILITY
OFF COMP1
OFF compressor 1
OFF COMP2
OFF compressor 2
OFF (1)
When used for temperature control
OFF (2)
When used for temperature control and/or
antifreeze
OFF RES1
OFF heater 1
OFF RES2
OFF heater 2
Alarm code
Name of alarm
Bypass
activation event
Bypass time
SET
activation
Hyster
esis
Automatic
alarm
time
(NOTE 1)
No.
interventi
ons time
Control
sensor
Er03
High pressure
(analogue)
None None
AL25
AL27
Not
present
AL43
High pressure
probe
Er07
Low pressure
(analogue)
Compressor
switches on or 4-
way valve
reverses
AL28
AL24
AL26
Not
present
AL29
Low pressure
probe
Er30
Internal circuit
antifreeze
On/Off (local or
remote), input in
heat mode
(NOTE 2)
AL15
AL12
AL13
Not
present
AL11
Internal
exchanger
water/air
outlet
temperature
Er31
External circuit
antifreeze
On/Off (local or
remote), input in
heat mode
(NOTE 2)
AL47
AL45
AL46
Not
present
AL44
External
exchanger
water outlet
temperature
Er35
High
temperature
None None
AL21
AL22
AL23
Automatic
reset
Internal
exchanger
water/air
outlet
temperature