UST500 CONTROL
06MC0074@00B0100
14/04/2010
79
Minimum temperature control setpoint in Cool
To modify the minimum temperature control setpoint in Cool mode.
Maximum temperature control setpoint in Cool
To modify the maximum temperature control setpoint in Cool mode.
Minimum temperature control setpoint in Heat.
To modify the minimum temperature control setpoint in Heat mode.
Maximum temperature control setpoint in Heat.
To modify the maximum temperature control setpoint in Heat mode.
Temperature control hysteresis in Cool
Temperature control hysteresis in Heat
To modify temperature control hysteresis in Cool/Heat modes.
Steps/compressors insertion differential in Cool
Steps/compressors insertion differential in Heat
To modify the steps/compressors insertion differential in Cool/Heat modes
Select probe for temperature control differential in Cool
Select probe for temperature control differential in Heat
To select the probe for the temperature control differential in Cool/Heat modes
Value
Probe 1
Probe 2
0
NTC input for internal exchanger water/air inlet temperature
(CF12…CF15=1)
External temperature NTC input
(CF12…CF15=6)
1
NTC input for internal exchanger water/air outlet temperature
(CF12…CF15=2)
2
NTC input for external exchanger water/air inlet temperature
(CF12…CF15=3)
3
NTC input for external exchanger water/air outlet temperature
(CF12…CF15=4)
Enable block heat pump function
To enable or disable the heat pump block
•
0 = Heat pump block disabled
•
1 = Heat pump block enabled
Block heat pump set point
To set the heat pump block setpoint
Heat pump block hysteresis
To modify the heat pump block hysteresis
Setpoint differential in Cool from start of Economy
To modify the setpoint differential in Cool mode from Economy input
Setpoint differential in Heat from start of Economy
To modify the setpoint differential in Heat mode from Economy input
Function mode selection parameters (St)
Select function modes
To select the function mode.
•
0 = cool only
•
1 = heat only
•
2 = heat and cool
Enable changeover from analogue input.
To enable operating mode changeover from analogue input.
•
0 = not enabled
•
1 = enabled
Select probe for automatic changeover of operating mode.
To select the probe for automatic changeover of the operating mode.
•
0 = external temperature
•
1 = inlet water temperature
•
2 = outlet water temperature
Differential for automatic mode change in Heat
To modify the differential for the automatic mode change in Heat mode.
Differential for automatic mode change in Cool
To modify the differential for the automatic mode change in Cool mode.
Compressor Parameters (CP)
Compressor type
To select the type of compressor
•
0 = simple (1 step)
•
1 = 2 step partialized
Number of compressors per circuit
To select the number of compressors per circuit.
•
1 = 1 compressor
•
2 = 2 compressors
tr06
tr07
tr08
tr09
tr10
tr11
tr12
tr13
tr14
tr15
tr16
tr17
tr18
tr19
tr20
St00
St01
St02
St03
St04
CP00
CP01