UST500 CONTROL BOARD
52 06MC0074@00B0100
14/04/2010
Internal exchanger electric heaters (folder PAr/HI)
Parameters for internal circuit exchanger heaters can be viewed and configured in folder HI: Internal circuit electric heater parameters (see User
Interface and Parameters chapters).
Antifreeze/integrated use heaters should be connected to a relay output (°) DO1..D04, D06 (see).
•
They are active only when the relative parameter enabling them HI00, HI02=1 (see table)
•
In Std-by the antifreeze heaters can be enabled by configuring HI01=1 (see table)
•
In defrost, the antifreeze heaters can be enabled by configuring HI03=1 (see table)
(°) When configuring the machine with two internal exchanger electric heaters, configure two outputs:
•
one output as internal exchanger heater 1
•
one output as internal exchanger heater 2
Two internal exchanger electric heaters can be configured in parameter HI04
Heaters
Parameter
Description
Value
0
1
Antifreeze (°)
HI00
Enable internal exchanger heaters for antifreeze
Heaters disabled
Heaters enabled
(°)
Antifreeze
(Standby mode)
HI01
Enable internal exchanger heater regulator in
standby for antifreeze
Heaters disabled
Heaters enabled
Integrated use
HI02
Enable integrated use of internal exchanger heaters
Heaters disabled
Heaters enabled
See Defrost
chapter
HI03
Enable force heaters on during defrost.
Heaters enabled on
request of
temperature
controller (antifreeze
or integrated use)
Heaters ALWAYS
enabled during
defrost
Antifreeze
HI05
Select probe for heater control.
Internal exchanger for antifreeze
Temperature
water or air
Internal exchanger
inlet
Temperature
water or air
internal exchanger
outlet
Antifreeze
HI06
Electric heater regulator setpoint
Internal exchanger for antifreeze
Range set in parameters HI07..HI08
Hysteresis set in parameter HI09
Heaters
Parameter
Description
Value
1
2
Integrated use /
antifreeze
(heater 1
only) (°°)
HI04
Number of internal exchanger heaters
1 Heater enabled 2 heaters enabled
N.B.:
(°) set H00=1 even when heaters are to be integrated
(°°) FOR ANTIFREEZE, when configuring the machine with two internal exchanger electric heaters, only heater 1 will be activated.