CONTROLLO UST500
78 06MC0074@00B0100
14/04/2010
Select main display
To select to view the main display.
0
Analogue input 1
4
Clock
1
Analogue input 2
5
Setpoint set
2
Analogue input 3
6
Real setpoint
3
Analogue input 4
Enable manual defrost from key
To enable or disable manual defrost ([UP] key) (manual defrost function) from a key.
•
0 = Key not enabled for the function
•
1 = Key enabled for the function
Enable mode function from key
To enable or disable mode selection ([esc] key) (mode function) from a key.
•
0 = Key not enabled for the function
•
1 = Key enabled for the function
Enable disp function from key
To enable or disable configuration of the main display from a key [set] (disp function).
•
0 = Key not enabled for the function
•
1 = Key enabled for the function
Enable “ON/OFF” function from key
To enable or disable the switching on or off of the device from a key [DOWN] (ON/OFF function).
•
0 = Key not enabled for the function
•
1 = Key enabled for the function
Enable “set” function from key.
To enable or disable access via the “set” key to machine state menu and relative subfolders.
•
0 = Key not enabled for the function
•
1 = Key enabled for the function
Parameter
Key
[Press and hold]
Default icon
on front panel
UI10 [UP]
UI11 [esc]
mode
UI12 [set]
disp
UI13 [DOWN]
Parameter
Key
(press and release)
Default icon
on front panel
UI14 set
None
(set key)
Installation password
Installation password
Manufacturer password
Manufacturer password
Temperature control parameters (tr) – temperature controller
Type of temperature controller
To set the type of temperature controller.
•
0 = Proportional
•
1 = Differential
•
2 = Digital
Enable heat pump
To enable or disable the heat pump.
•
0 = Heat pump absent
•
1 = Heat pump present
Select temperature control probe in Cool
Select temperature control probe in Heat
To select the temperature control probe in Cool/Heat modes.
•
0 = NTC input for internal exchanger inlet water/air temperature
•
1 = NTC input for internal exchanger water outlet temperature
•
2 = NTC input for external exchanger water inlet temperature
•
3 = NTC input for external exchanger water outlet temperature
•
4 = High pressure input
•
5 = Low pressure input
Temperature control setpoint in Cool
Temperature control setpoint in Heat
To modify temperature control setpoint in Cool/Heat modes.
UI09
UI10
UI11
UI12
UI13
UI14
UI17
UI18
tr00
tr01
tr02
tr03
tr04
tr05