UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
31
Table B – Outputs: Configuration table
The polarity of is defined as listed below:
Value
Description
+ Positive
Active when contact closed
- Negative
Active when contact open
Value
Description
0 Output
disabled
±1 Compressor
1
±2 Output
step
2
±3
Internal circuit water pump
±4
External circuit water pump
±5 Reversing
valve
±6 Boiler
±7
Internal circuit electric heater 1
±8
Internal circuit electric heater 2
±9
External circuit electric heater
±10
Auxiliary electric heater
±11
External exchanger fan
±12 Recirculation
fan
±13 Alarm
If multiple outputs are configured to run the same resource, the outputs will be activated in parallel.
Configuration of analogue outputs
See the chapter on Electric Connections for the number and type of analogue outputs used and for information on the
symbols used on labels supplied with the device.
There are 4 analogue outputs. 1 high voltage one and 3 low (SELV) voltage ones, the exact number depending on the following models and
with the following characteristics:
Table A – Analogue outputs and Models
High voltage
SELV
Models
Output
2A 230V
PWM
0-10V /
4..20mA
S
T
542/
C
S
T
552/
C
TC1
●
●
AO1
●
●
●
AO2
●
●
AO3
●
Triac analogue output (TC1)
Available only in models with 4 relays
High voltage output generally used to pilot fans or water pumps.
The output can be configured for proportional operation (constant speed variation) or as ON/OFF.
Remote control switches downstream from the Triac are NOT permitted.
The TC1 output can be configured as described in the table “Analogue Output TC1 - AO1 AO2 : configuration table”
Configuration of low voltage (SELV) analogue output
•
AO1 always available
o
If configured as digital, see parameter CF51
•
AO2
see
models chapter
o
If configured as digital, see parameter CF52
They can be configured as:
o
PWM (via CFS modules) or
o
open collector (On/Off).
•
AO3 - low voltage (SELV) output to pilot external modules to run fans
Can be used to pilot 4-20mA fans or 0-10V fans (via parameter CF30)
To configure, see the table below. All analogue outputs can be configured as digital or proportional.
Relay and open
collector output:
Configuration
table
Analogue outputs