UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
67
Digital alarms
Alarm
code
Name of alarm
Bypass
activation event
Bypass
time
Automatic
alarm
activation time
Manual alarm
activation
time
Exit alarm
deactivation
time
Number of
interventions per
sample time
Er01
High Pressure
Alarm
None
not present
not present
not present
not present
AL03
Er05
Low Pressure
Alarm
Circuit
compressor
activated or
reversal of 4-way
valve (NOTE 1)
AL02
not present
not present
not present
AL01
Er20
Internal circuit flow
meter alarm
Internal circuit
pump activation
AL05
AL06
AL04
AL07
not present
Er25
External flow
switch alarm
External circuit
pump activation
AL37
AL38
AL36
AL39
not present
Er10
Compressor 1
thermoswitch
Compressor
switched on
AL09
not present
not present
not present
AL08
Er11
Compressor 2
thermoswitch
Compressor
switched on
AL09
not present
not present
not present
AL08
Er41
External
exchanger fan
thermoswitch
None Not
present
Not present
not present
Not present
AL10
Er40
Internal exchanger
fan thermoswitch
None Not
present
Not present
not present
Not present
AL35
Er15
Compressor 1 oil
pressure switch
Compressor 1
switched on
AL48
Not present
not present
Not present
AL42
Er16
Compressor 2 oil
pressure switch
Compressor 2
switched on
AL48
Not present
not present
Not present
AL42
Er21
Internal circuit
pump
thermoswitch
None Not
present
Not present
not present
Not present
AL40
Er26
External circuit
pump
thermoswitch
None Not
present
Not present
not present
Not present
AL41
Er50
Internal exchanger
electric heater
thermoswitch
None Not
present
Not present
not present
Not present
not present
Er51
Internal exchanger
electric heaters
thermoswitch 2
None Not
present
Not present
not present
Not present
not present
Er52
External
exchanger electric
heater
thermoswitch
None Not
present
Not present
not present
Not present
not present
Er56
Auxiliary heaters
thermoswitch
None Not
present
Not present
not present
Not present
not present
(NOTE 1) The bypass is activated by the reversal of the 4-way valve only if at least one compressor is on.
During defrost, the low pressure alarm is disabled if Pa AL20 = 0.