UST500 CONTROL BOARD
06MC0074@00B0100
14/04/2010
43
For partialized compressors only - Minimum ON step during decrease in output (CP09)
If there is only one compressor in the installation, the minimum time between the switching off of the compressor and its partialization are
observed (CP09).
Minimum OFF step during decrease in output
(CP09)
Minimum time between switching off and on of the same compressor (CP03)
Compressor OFF-ON timing
After switching off, a compressor can switch back on again after the delay (in seconds) set in parameter CP03 (Minimum switch off-switch on
time for the same compressor);
This time delay also applies when UST is started up.
When the device is switched on for the first time, the default sequence is run time 1 - see Compressor on/off sequence/Run time sequence
(i.e. the device behaves as if CP02=5);
Minimum time between the switching on of the same compressor (CP04)
Compressor ON-ON timing
After switching off, a compressor can switch back on again after the delay (in seconds) set in parameter CP04 (Minimum time between the
switching on of the same compressor)
This time delay also applies when UST is started up.
When the device is switched on for the first time, the default sequence is run time 1 - see Compressor on/off sequence/Run time sequence
(i.e. the device behaves as if CP02=5);
Minimum compressor ON time
The time required to switch the same compressor on is set in parameter CP07 (Minimum compressor switch on time);